Washington DC Data Centre

Commitment to Compliance

CenturyLink is dedicated to continuously improving and maintaining compliance and standards that are critical to customers.

Washington DC Area Data Centres: Supporting Global Connections

Washington DC is home to Fortune 500 companies and some of the most important financial institutions in the world. It also hosts the largest IP peering connection point in North America.

Six of the 60+ CenturyLink data centres are located in metro Washington DC. Combined, the Washington DC data centres supply 329,000 sq/ft of premium colocation space that empowers this vital communications nucleus. Designed to meet strict networking and IT security demands of enterprise, government and financial institutions, the Washington DC data centres offer failsafe critical systems infrastructure, powerful cross connects, and multi-tier security measures that can be augmented for specific security requirements. From these facilities, technology connects markets across the globe.

Announcements

Take a Virtual Tour of our CH3 Data Centre

Data Centres

Washington DC Data Centre Locations

Locations

DC2: Sterling, VA

Space: 88,489 sf   Power: 6 MW

Tech Specs

DC2: Sterling, VA     Space: 88,489 sf     Power: 6 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 88,489
  • Raised floor (inches) = 12

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 6 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilizes two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N +1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC3: Sterling, VA

Space: 78,671 sf   Power: 8 MW

Tech Specs

DC3: Sterling     Space: 78,671 sf     Power: 8 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior(sf) = 78,671
  • Raised floor (inches) = 24

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1 + 1
  • Total Power Capacity = 8 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilizes two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC4: Sterling, VA

Space: 135,513 sf   Power: 12 MW

Tech Specs

DC4: Sterling     Space: 135,513 sf     Power: 12 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 135,513
  • Raised floor (inches) = 30

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1 + 1
  • Total Power Capacity = 12 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilizes two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC5: Sterling, VA

Space: 47,508 sf   Power: 3.2 MW

Tech Specs

DC5: Sterling     Space: 47,508 sf     Power: 3.2 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 47,508
  • Raised floor (inches) = 24

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 3.2 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilizes two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC6: Sterling, VA

Space: 71,033 sf   Power: 13.6 MW

Tech Specs

DC6: Sterling     Space: 71,033 sf     Power: 13.6 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 71,033
  • Raised floor (inches) = 24

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 13.6 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilizes two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

DC7: Sterling, VA

Space: 135,243 sf   Power: 4.8 MW

Tech Specs

DC7: Sterling     Space: 135,243 sf     Power: 13.6 MW

Real Estate Summary

  • Located near Dulles International and Reagan National Airports; 40 minutes from Washington, D.C.
  • One story building
  • Total building interior (sf) = 135,243
  • Raised floor (inches) = 36

Electrical Summary

  • Dominion Virginia Power provides power feeds
  • Power density minimum (W/sf) = 150
  • Generator configuration = N + 1
  • Total Power Capacity = 4.8 MW
  • Minimum two fuel replenishing companies

Fire Detection and Suppression Summary

  • VESDA provides early warning detection
  • Pre-Action system utilizes two detection methods; one ionized and one photo electric detector interlocked with the dry pipe sprinkler system

Mechanical Summary

  • Cooling system configuration = N + 1
  • CenturyLink manages temperature and humidity to strict ASHRAE standard

More Locations

Over 60 Data Centre Locations Worldwide

Latest from the EpiCenter Blog

Active-active vs. Active-passive: Which Data Center Architecture has the Advantage for Disaster Recovery? – Part 2

Nader Hantour | February 23,2017

As I noted in part one of this blog, active-active and active-passive data center architectures are often used in businesses' disaster recovery and business continuity plans. Without such plans in place, companies may face outages which hurt them financially while … Read more…→ The post Active-active vs. Active-passive: Which Data Center Architecture has the Advantage for Disaster Recovery? - Part 2 appeared first on CenturyLink EpiCenter Blog.

Active-active vs. Active-passive: Which Data Center Architecture has the Advantage for Disaster Recovery? – Part 1

Nader Hantour | February 21,2017

Companies in multiple industries continue to utilize colocation for their mission-critical IT infrastructure and data due to the scalability, reliability, resiliency and security it provides. It enables them to enjoy increased bandwidth, higher network speed and connectivity, carrier diversity, remote … Read more…→ The post Active-active vs. Active-passive: Which Data Center Architecture has the Advantage for Disaster Recovery? - Part 1 appeared first on CenturyLink EpiCenter Blog.

Data Centre Connectivity: Continual Improvement

Christian Pedersen | February 20,2017

Companies that utilize colocation need to have access to strong network connectivity, especially with the rapidly increasingly amounts of data prompted by "big data" and the Internet of Things (IoT). This enables them to keep connected with their customers through … Read more…→ The post Data Centre Connectivity: Continual Improvement appeared first on CenturyLink EpiCenter Blog.